1. What the interface fixes before anything else
Neither product is a bracket-mounted arrester. Each is a complete elbow: semiconducting shield, EPDM insulation, MOV column, probe and ground lead moulded into one body that pushes onto a bushing insert. The electrical ratings sit inside a shape that IEEE Std 386 defines, so the shape has to be settled before the rating table is worth reading.
Cooper catalogues its 35 kV part as 35 kV Class Interface 1A, Large Interface and describes the mating interface as 200 A loadbreak. Chardon labels the 35L-LEA as 35 kV Large Interface and states compliance with IEEE Std 386 without naming the current rating of the interface. Both seat on the same 35 kV large-interface bushing, and both are deadfront, submersible and operable with a clampstick.
3238018C18M in 15 kV class, 3238019C18M in 25 kV class and 3238020C18M in 35 kV class large interface. The rating is identical on all three; only one seats on a 35 kV large-interface bushing. The reverse error is just as common: a 35 kV-rated arrester in a 25 kV body, bought on rating alone and found not to fit on site.That distinction is why this comparison starts with bodies and only then compares numbers. It is also why a cross reference that lists only voltage ratings is not usable for procurement.
2. Rating coverage: nine against seven
Chardon builds one 35 kV large-interface body and rates it nine ways. Cooper builds one body and rates it seven ways. The overlap is six ratings: 18, 21, 24, 27, 30 and 36 kV. The complete ordering table, electrical data and outline drawing for the Chardon part are on the 35L-LEA product page.
| Duty cycle (kV) | MCOV (kV) | Chardon 35L-LEA | Cooper M.O.V.E. |
|---|---|---|---|
| 10 | 8.4 | 35L-LEA 10 | — |
| 12 | 10.2 | 35L-LEA 12 | — |
| 15 | 12.7 | 35L-LEA 15 | — |
| 18 | 15.3 | 35L-LEA 18 | 3238020C18M |
| 21 | 17.0 | 35L-LEA 21 | 3238020C21M |
| 24 | 19.5 | 35L-LEA 24 | 3238020C24M |
| 27 | 22.0 | 35L-LEA 27 | 3238020C27M |
| 30 | 24.4 | 35L-LEA 30 | 3238020C30M |
| 33 | 27.0 | — | 3238020C33M |
| 36 | 29.0 | 35L-LEA 36 | 3238020C36M |
Source: Chardon data sheet 35L-LEA rev. 111226, Table 1; Eaton catalog data CA235025EN (effective May 2017), Table 3. Cooper catalogue numbers follow the pattern 3238020CxxM. Dash = rating not offered in this interface.
The three ratings Chardon adds are the practical reason this comparison exists. A 13.8 kV system built with 35 kV large-interface apparatus needs a low duty rating in a large body: 35L-LEA 10 or 35L-LEA 15 does that with no adapter. Cooper offers 10, 12 and 15 kV duty ratings, but only in 15 kV and 25 kV class bodies, so the electrical match is available and the mechanical match is not. Chardon has no 33 kV rating; a specification that calls for 33 kV lands on the Cooper column by default.
3. Protective level: the same numbers on paper
This is the part most comparisons get wrong, because the two tables are usually compared page by page instead of value by value. Put side by side, every shared rating agrees in every column: equivalent front-of-wave, and maximum discharge voltage at 1.5, 3, 5, 10 and 20 kA.
| Duty cycle (kV) | MCOV (kV) | Front of wave (kV crest) | 1.5 kA | 3 kA | 5 kA | 10 kA | 20 kA | Offered by |
|---|---|---|---|---|---|---|---|---|
| 10 | 8.4 | 33.0 | 27.0 | 29.1 | 31.2 | 34.1 | 38.9 | Chardon only |
| 12 | 10.2 | 41.5 | 33.9 | 36.6 | 39.2 | 42.9 | 48.9 | Chardon only |
| 15 | 12.7 | 51.8 | 42.4 | 45.7 | 49.0 | 53.6 | 61.1 | Chardon only |
| 18 | 15.3 | 62.2 | 50.9 | 54.9 | 58.8 | 64.3 | 73.4 | Both |
| 21 | 17.0 | 66.0 | 54.0 | 58.2 | 62.4 | 68.2 | 77.9 | Both |
| 24 | 19.5 | 77.0 | 63.0 | 67.9 | 72.8 | 79.6 | 90.8 | Both |
| 27 | 22.0 | 87.2 | 71.4 | 76.9 | 82.4 | 90.1 | 103.0 | Both |
| 30 | 24.4 | 97.1 | 79.5 | 85.7 | 91.8 | 100.0 | 115.0 | Both |
| 33 | 27.0 | 108.0 | 87.8 | 95.1 | 102.0 | 112.0 | 127.0 | Cooper only |
| 36 | 29.0 | 116.0 | 95.3 | 103.0 | 110.0 | 120.0 | 137.0 | Both |
Discharge voltages are kV crest at 8/20 µs. Values are identical in the two publications for all six shared ratings, and identical again for 10, 12 and 15 kV against the same-rated Cooper arresters in their 15 kV and 25 kV class bodies.
The identical columns are not a rounding coincidence. Residual voltage tracks MCOV, not the duty-cycle rating, and both product lines produce between 4.58 and 4.81 kV of 20 kA discharge voltage for every kV of MCOV. Read that way the table collapses into two families: the 12, 15 and 18 kV ratings sit near 4.80 × MCOV, and the 21 to 36 kV ratings sit near 4.67 × MCOV, because the MCOV-to-rating ratio drops from about 0.85 to about 0.81 over that range.

Two conclusions follow. First, on protective level there is nothing to choose between the two lines at a given rating, so insulation coordination does not decide the purchase. Second, agreement on paper is not independent evidence. The Chardon sheet reproduces the Cooper table structure and wording closely enough that the numbers should be treated as a declared equivalence, not as two separate laboratories arriving at the same result. A tender that accepts either product should ask for the type-test reports to IEEE C62.11 rather than compare data sheets.
4. TOV: two curves, two bases
Temporary overvoltage is where the documents stop being interchangeable, and where a careless comparison produces the wrong answer.
Cooper publishes Figure 2 with the vertical axis in per-unit MCOV from 1.0 to 2.2 and the horizontal axis from 0.01 s to 10,000 s, no prior duty at 85 °C. The curve starts near 2.1× MCOV at 0.01 s, falls to about 1.65× at 0.1 s, and is still around 1.3× MCOV at 10,000 s. An IEEE C62.22 minimum curve is plotted underneath for reference.
Chardon publishes a curve whose vertical axis is marked UR over a 0.85 to 1.20 band, with time from 0.1 s to 7200 s. Read as per-unit MCOV, that curve would put the capability below 1.0 × MCOV after a few hundred seconds, which no arrester can do, because MCOV is by definition the voltage it holds continuously. The axis therefore has to be per-unit rated voltage, and the two curves cannot be read against each other without converting.
| Duty (kV) | MCOV (kV) | 1.20 UR (kV) | → pu MCOV | 0.85 UR (kV) | → pu MCOV |
|---|---|---|---|---|---|
| 36 | 29.0 | 1.20 × 36 = 43.2 | 43.2 / 29.0 = 1.49 | 0.85 × 36 = 30.6 | 30.6 / 29.0 = 1.06 |
| 24 | 19.5 | 1.20 × 24 = 28.8 | 28.8 / 19.5 = 1.48 | 0.85 × 24 = 20.4 | 20.4 / 19.5 = 1.05 |
| 15 | 12.7 | 1.20 × 15 = 18.0 | 18.0 / 12.7 = 1.42 | 0.85 × 15 = 12.8 | 12.8 / 12.7 = 1.00 |
Conversion from the Chardon curve ends to a per-unit MCOV basis. Over the 0.1 s to 7200 s window that both curves cover, Chardon runs from about 1.49 down to 1.06 × MCOV and Cooper from about 1.65 down to about 1.30. Cooper's curve also extends to 0.01 s, where it reaches about 2.1 × MCOV.
Normalised, Cooper's published TOV envelope is higher across the whole range, by roughly 0.2 × MCOV at 100 s. Eaton markets this directly in bulletin B235-11029, "Make the Move to the Highest TOV Rated Elbow Arrester in the Industry". That is a manufacturer claim, but it is consistent with the published curve, and the Chardon sheet does not contradict it.
5. Construction and installation
Both bodies are built the same way in the essentials: peroxide-cured EPDM insulation mixed in-house, a moulded semiconducting EPDM shield to IEEE Std 592, an MOV column bonded with silver-loaded epoxy, a stainless steel pulling eye for clampstick work and a #4 AWG copper ground lead. The differences are in the details that decide a retrofit.
| Item | Chardon 35L-LEA | Cooper M.O.V.E. |
|---|---|---|
| End cap | Stainless steel cap, weatherproof seal and ground-lead connection | Brass cap, magneformed around moulded-in sealing rings |
| Internal current path | Multi-disk MOV module, silver-loaded epoxy bonds; semiconducting insert shields the connector | Welded flexible tin-plated copper leads from probe to column, spring shunt and extra-long loading spring |
| Ground lead | #4 AWG flexible copper, length not published | #4 AWG, 36 in (914 mm), woven construction |
| Visible-break variant | Not offered in the published range | POSI-BREAK M.O.V.E. version, same installation instruction MN235020EN |
| 600 A feeder integration | Not documented | Elbow arresters on T-OP II and BT-TAP systems |
| Standards cited | IEEE Std 386 (housing), IEEE Std 592 (shield) | IEEE Std 386-2006, IEEE Std C62.11-2005, IEEE Std 592-2007 |
| Design tests published | Duty cycle, high-current short-duration, low-current long-duration (named, without parameters) | 22 × 5 kA 8/20 µs; 2 × 40 kA 4/10 µs; 20 × 75 A 2000 µs, with thermal-stability criteria |
Compiled from the two manufacturer data sheets. Items marked as not published were absent from the documents, not confirmed absent from the product.
The ground lead is the item most often missed in a switch-out. Cooper ships 914 mm as standard; Chardon does not state a length. If the existing installation lands on a specific ground stud, a lead that is short by 100 mm turns a one-hour job into a cable re-termination.
The standards line matters for a tender. Cooper's sheet states C62.11-2005 compliance explicitly. Chardon's sheet states IEEE 386 for the housing and IEEE 592 for the shield, and lists the same production tests, but never names C62.11. The tests are there; the declaration is not. If the specification requires a C62.11 statement, ask for it in writing rather than inferring it from the test list.
6. Installed envelope: 2 mm apart, 98 mm apart
The two outline drawings do not overlay, and the reason is worth understanding before a substitution is approved.
| Dimension | Chardon (mm) | Cooper (mm) | Remark |
|---|---|---|---|
| Overall height | 436 | 338 (A) | Not like-for-like; see note |
| Body height | 375 | 284 (B) | 91 mm difference if the same feature |
| Horizontal extent | 266 | 264 (C) | Agrees within 2 mm |
| Pulling eye to body axis | 118 | not published | Chardon only |
| Body outside diameter | Ø78 | 55 at the lower end | Different features, do not compare |
| Interface dimension S3 | not published | 120 | Cooper only, 35 kV class |
Chardon figures from the 35L-LEA outline drawing; Cooper figures from Figure 3 and Table 3 of CA235025EN. Each set is dimensioned to its own drawing conventions.
The horizontal numbers agree: 266 mm against 264 mm. Whatever else differs, the two bodies occupy the same plan footprint, which is what matters for cable-train and cabinet depth. The vertical numbers do not agree: 436 mm against 338 mm overall, and 375 mm against 284 mm for the body.
Two explanations are possible. Either the Chardon body is genuinely about 90 mm longer, or the two drawings dimension different features and one includes a cap or skirt the other excludes. The published documents do not settle it. In a pad-mounted cabinet with a fixed bushing height, 90 mm is the difference between a seated elbow and an elbow that fouls the roof or the cable support, so this is a drawing question, not a table question. Overlay both outlines in the installed attitude before approving a substitution.
The diameter comparison is a trap in the other direction. Chardon quotes Ø78 mm for the insulated body; Cooper quotes 55 mm at the lower end, next to the cap. They are not the same feature and should not be used to judge clearance.
7. Cross reference, rating by rating
The table below maps the two lines by interface and duty rating. It is the table to use for a substitution study, with the qualifications that follow it.
| Chardon | Cooper / Eaton | Basis of the match |
|---|---|---|
| 35L-LEA 10 | — | No Cooper equivalent in this interface. 3238018C10M is 15 kV class. |
| 35L-LEA 12 | — | No Cooper equivalent. 3238018C12M is 15 kV class. |
| 35L-LEA 15 | — | No Cooper equivalent. 3238019C15M is 25 kV class. |
| 35L-LEA 18 | 3238020C18M | Direct: same interface, same MCOV 15.3 kV, same discharge table |
| 35L-LEA 21 | 3238020C21M | Direct: MCOV 17.0 kV |
| 35L-LEA 24 | 3238020C24M | Direct: MCOV 19.5 kV |
| 35L-LEA 27 | 3238020C27M | Direct: MCOV 22.0 kV |
| 35L-LEA 30 | 3238020C30M | Direct: MCOV 24.4 kV |
| — | 3238020C33M | No Chardon equivalent: the 35L-LEA range skips 33 kV |
| 35L-LEA 36 | 3238020C36M | Direct: MCOV 29.0 kV |
Derived from the two published catalogues. This is an engineering equivalence by interface and rating, not a manufacturer-issued interchange list.
What the table does and does not guarantee:
- Interface: guaranteed. Both are 35 kV class large interface to IEEE Std 386, and both are designed for a 200 A loadbreak bushing.
- Rating and MCOV: guaranteed at the six shared points, and the discharge voltages are published as identical.
- TOV and energy duty: not guaranteed. Cooper publishes a higher envelope; Chardon publishes a curve on a different base. Check against the fault and switching study.
- Envelope: not guaranteed. The vertical dimensions differ by roughly 90 mm on paper.
- Accessories and documentation: not guaranteed. Ground-lead length, the POSI-BREAK option, the 600 A ecosystem and the C62.11 declaration all sit on the Cooper side.
One point on provenance, because it matters if this table is pasted into a specification. Eaton publishes its own elbow arrester cross reference tables as R235-68-1, covering other manufacturers. Chardon publishes an ANSI/IEEE part number reference chart, but the revision reviewed here covers connectors and elbows, not arresters. Neither manufacturer has issued an arrester cross reference for the other, so the table above is built from the primary catalogues and should be presented as such.
8. Choosing between them
With protective level equal and the interface shared, the decision usually turns on coverage, envelope and documentation rather than on the arrester itself.
| Requirement | Selection | Reason |
|---|---|---|
| 13.8 kV or 13.2 kV system with 35 kV large-interface bushings | Chardon 35L-LEA 10 / 12 / 15 | The only sub-18 kV ratings available in this body |
| 33 kV duty required | Cooper 3238020C33M | Chardon has no 33 kV rating |
| TOV is the binding constraint | Cooper, subject to a Chardon data request | Higher published TOV envelope on a per-unit MCOV basis |
| Visible-break or 600 A feeder integration | Cooper POSI-BREAK / T-OP II / BT-TAP | No Chardon equivalent documented |
| Second source for an existing Cooper installation | Chardon 35L-LEA at the same rating | Identical discharge voltages and interface; verify the envelope |
| Tight cabinet height or existing bracket | Either, after drawing overlay | 90 mm vertical difference on the published outlines |
| Tender requires an explicit C62.11 declaration | Cooper as catalogued, or Chardon with a written declaration | Only Cooper states C62.11-2005 on the data sheet |
For a standard 34.5 kV loop with 35 kV large-interface apparatus, the two products are interchangeable on paper, and the choice comes down to price, availability and which manufacturer's documentation the utility accepts. For anything outside 18 to 36 kV in this interface, the range decides by itself. The MCOV and TOV selection logic behind these tables is set out in the surge arrester selection guide.
9. FAQ
Is the Chardon 35L-LEA a direct replacement for a Cooper 3238020CxxM?
At 18, 21, 24, 27, 30 and 36 kV it matches interface, MCOV and published discharge voltage. It is not a drop-in replacement until the installed envelope and the TOV duty are checked, because the published vertical dimensions differ by about 90 mm and the TOV curves are drawn on different bases.
What does “large interface” mean on a 35 kV elbow arrester?
It is the 35 kV class separable interface defined by IEEE Std 386, which is physically larger than the 15 kV and 25 kV class 200 A interfaces. Cooper labels it Interface 1A, Large Interface. It is not the 600 A deadbreak interface and it does not accept a 25 kV class elbow.
Can a 25 kV elbow arrester be used on a 35 kV large-interface bushing?
No. The electrical rating may look adequate for a 34.5 kV system, but the body will not seat. Cooper's 3238019C18M is exactly this case: 18 kV duty in a 25 kV class body.
Why is there no Chardon 33 kV rating?
The published range runs 10, 12, 15, 18, 21, 24, 27, 30 and 36 kV. No reason is given in the data sheet. Where 33 kV is specified, the Cooper 3238020C33M is the only option in this interface.
Are the discharge voltages really identical?
For the six shared ratings, yes, in all six columns from front-of-wave to 20 kA. The values also match Cooper's 10, 12 and 15 kV arresters in other interface sizes. Treat that as a declared equivalence and ask for type-test reports if the difference matters to the specification.
How should the two TOV curves be compared?
Convert both to per-unit MCOV. Cooper's curve is already on that basis. Chardon's vertical axis is per-unit rated voltage, so multiply by the rating and divide by MCOV, which for these ratings is about 0.81 to 0.85 of rated. On that basis Cooper's curve sits roughly 0.2 per-unit MCOV higher at 100 s.
Documents used
- Eaton, Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester, catalog data CA235025EN, effective May 2017: Tables 1–3, Figures 2–3.
- Chardon Group, 35 kV Large Interface Elbow Arresters 35L-LEA, data sheet rev. 111226: ordering table, electrical characteristics, outline dimensions, TOV curve.
- IEEE Std 386 (separable insulated connector systems), IEEE Std C62.11 (metal oxide surge arresters), IEEE Std C62.22 (application guide), IEEE Std 592 (exposed semiconducting shields).
- Eaton bulletin B235-11029 (TOV claim) and R235-68-1 (elbow arrester cross reference tables).
Not verified in this comparison: type-test reports, TOV capability in per-unit MCOV for the Chardon product, unit weights, and any agency listing. Values are as printed in the documents above; confirm against the current revision before purchase.