Product Code: 72.5-RDTA196-10 The Chardon T-body Surge Arrester, a fully screened and submersible arrester that serves as the rear connector for the 72.5 kV, 1250A Front T-body . It is designed to

What Are You Looking For?
Product Code: 35L-LEA
35 kV large interface elbow arrester to IEEE Std 386. Metal oxide varistor module moulded in a peroxide-cured EPDM rubber elbow, fully shielded and deadfront, for pad-mounted transformer and vault applications. Nine duty-cycle ratings from 10 kV to 36 kV.
Brand :
ChardonCatalog Number :
35L-LEAProduct Type :
Elbow ArresterStandard Interface :
35 kV Large Interface (IEEE Std 386)System Voltage :
35 kVDuty Cycle Range :
10 u2013 36 kVMCOV Range :
8.4 u2013 29.0 kVHousing Material :
Peroxide-cured EPDM rubberSemiconducting Shield :
Per IEEE Std 592Overall Length :
266 mmOverall Height :
436 mmBody Diameter :
u00d878 mmGround Lead :
#4 AWG flexible copperRatings Available :
9 (10 / 12 / 15 / 18 / 21 / 24 / 27 / 30 / 36 kV)Lead time :
4-8 weeksProduct Code: 72.5-RDTA196-10 The Chardon T-body Surge Arrester, a fully screened and submersible arrester that serves as the rear connector for the 72.5 kV, 1250A Front T-body . It is designed to
Product Code: 51-RDTA134 The Chardon T-Body Surge Arrester is an arrester combined within a coupling(rear) T-Body interface. It is designed to protect apparatus, including transformers, switchgear,
Product Code: 36-RDTA102-10-42 The Chardon T-Body Surge Arrester is an arrester combined within a coupling (rear) T-Body interface. It is designed to protect apparatus, including transformers,
Product Code: 36-RDTA102-10 The Chardon T-Body Surge Arrester is an arrester combined within a coupling (rear) T-Body interface. It is designed to protect apparatus, including transformers, swi
Product Code: 34-RDTA85 34-RDTA95-10 The Chardon T-Body Surge Arrester is an arrester combined within a coupling (rear) T-Body interface. It is designed to protect apparatus, including transformer
Product Code: 26-RDTA66 26-RDTA72-10 The Chardon T-Body Surge Arrester is an arrester combined within a coupling (rear) T-Body interface. It is designed to protect appa
Product Code: 17-RDTA50/17-RDTA45 The Chardon T-Body Surge Arrester is an arrester combined within a coupling(rear) T-Body interface. It is designed to protect apparatus, including transformers, sw
Product Code: GLE200 The Chardon 15 kV, 25 kV & 35 kV Grounding Elbow provide a circuit between energized and non-energized sections of the distribution line. The grounding elbow can be assemb
Chardon 35L-LEA is a 35 kV large interface elbow arrester built to IEEE Std 386. A metal oxide varistor (MOV) module is moulded inside a rubber elbow, so the arrester installs exactly like a loadbreak elbow — no separate bracket, no exposed gap, no hot work.
|
Protects the cable, not just the transformer
|
Mounted at the open point of a loop or at the end of a radial, the arrester clips switching and lightning surges before they travel down the cable. Both the cable insulation and the connected apparatus see a lower surge.
|
|
Deadfront and submersible
|
The MOV sits inside a peroxide-cured EPDM housing with a moulded semiconducting shield, so the assembly stays fully shielded and deadfront — suitable for vaults, pad-mounted cabinets and other locations where an exposed arrester is not acceptable.
|
|
Interchangeable with any IEEE 386 large interface
|
The large interface bushing entrance follows IEEE Std 386, so the 35L-LEA mates with existing 35 kV large interface apparatus bushings and inserts without adapters.
|
All nine ratings share the same 35 kV large interface body. Select by duty-cycle voltage; the MCOV rating follows directly from it.
| IEEE Std 386 standard interface | Duty cycle (kV) | MCOV rating (kV) | Catalog number |
|---|---|---|---|
|
35 kV
Large Interface |
10
|
8.4
|
35L-LEA 10
|
|
12
|
10.2
|
35L-LEA 12
|
|
|
15
|
12.7
|
35L-LEA 15
|
|
|
18
|
15.3
|
35L-LEA 18
|
|
|
21
|
17.0
|
35L-LEA 21
|
|
|
24
|
19.5
|
35L-LEA 24
|
|
|
27
|
22.0
|
35L-LEA 27
|
|
|
30
|
24.4
|
35L-LEA 30
|
|
|
36
|
29.0
|
35L-LEA 36
|
Discharge voltages are crest values for an 8/20 µs current wave. The equivalent front-of-wave value is the crest voltage for a 1 kA, 1×2 µs wave.
| Duty cycle rating (kV) | MCOV (kV) | Equivalent front of wave (kV crest) | Maximum discharge voltage (kV crest), 8/20 µs wave | ||||
|---|---|---|---|---|---|---|---|
| 1.5 kA | 3 kA | 5 kA | 10 kA | 20 kA | |||
|
10
|
8.4
|
33.0
|
27.0
|
29.1
|
31.2
|
34.1
|
38.9
|
|
12
|
10.2
|
41.5
|
33.9
|
36.6
|
39.2
|
42.9
|
48.9
|
|
15
|
12.7
|
51.8
|
42.4
|
45.7
|
49.0
|
53.6
|
61.1
|
|
18
|
15.3
|
62.2
|
50.9
|
54.9
|
58.8
|
64.3
|
73.4
|
|
21
|
17.0
|
66.0
|
54.0
|
58.2
|
62.4
|
68.2
|
77.9
|
|
24
|
19.5
|
77.0
|
63.0
|
67.9
|
72.8
|
79.6
|
90.8
|
|
27
|
22.0
|
87.2
|
71.4
|
76.9
|
82.4
|
90.1
|
103
|
|
30
|
24.4
|
97.1
|
79.5
|
85.7
|
91.8
|
100.0
|
115.0
|
|
36
|
29.0
|
116.0
|
95.3
|
103.0
|
110.0
|
120.0
|
137.0
|
Dimensions below are for the 35L-LEA body with a 35 kV large interface. All values in millimetres; confirm against the drawing before building cable trays, brackets or enclosure cut-outs.

| Dimension | mm | Note |
|---|---|---|
|
Overall length
|
266
|
maximum horizontal extent, pulling eye to elbow end
|
|
Overall height
|
436
|
top of arrester to base of terminal
|
|
Body height
|
375
|
upper shoulder to base of terminal
|
|
Length to body axis
|
118
|
pulling eye end to centre line of the vertical body
|
|
Body diameter
|
78
|
O.D. of the insulated body
|
Pick the duty-cycle rating that matches the system grounding arrangement. Table below follows the application guide in IEEE Std C62.22; values in brackets are the MCOV of that rating.
| System nominal voltage (kV rms) | Maximum voltage, range B (kV rms) | 4-wire multigrounded neutral wye | 3-wire low impedance grounded | Delta and 3-wire high impedance grounded |
|---|---|---|---|---|
|
6.90
|
7.26
|
-
|
-
|
9(7.65)
|
|
8.32 Y/4.80
|
8.80 Y/5.08
|
6(5.1)
|
9(7.65)
|
-
|
|
12.00 Y/6.93
|
12.7 Y/7.33
|
9(7.65)
|
12(10.2)
|
-
|
|
12.47 Y/7.20
|
13.20 Y/7.62
|
9(7.65) or 10(8.4)
|
15 (12.7)
|
-
|
|
13.20 Y/7.62
|
13.97 Y/8.07
|
10(8.4)
|
15 (12.7)
|
-
|
|
13.80 Y/7.97
|
14.52 Y/8.388
|
10(8.4) and 12(10.2)
|
15 (12.7)
|
-
|
|
13.80
|
14.52
|
-
|
-
|
18(15.3)
|
|
20.76 Y/12.00
|
22.00 Y/12.70
|
15 (12.7)
|
-
|
-
|
|
22.86 Y/12.00
|
22.00 Y/12.70
|
15 (12.7)
|
-
|
-
|
|
24.94 Y/14.40
|
26.40 Y/15.24
|
18 (15.3)
|
-
|
-
|
|
27.60 Y/15.935
|
29.255 Y/16.89
|
21 (17.0)
|
-
|
-
|
|
MOV module
|
Metal oxide varistor block set inside the elbow. Determines the protective level and the energy the arrester can absorb.
|
|
Insulation layer
|
Peroxide-cured EPDM, mixed and formulated in-house so the rubber characteristics stay under the manufacturer's control.
|
|
Semiconducting shield
|
Precision-moulded peroxide-cured semiconducting rubber, meeting the shield requirements of IEEE Std 592 and keeping the surface at ground potential.
|
|
Semiconducting insert
|
Moulded insert around the compression connector gives corona-free electrostatic shielding at the bushing interface.
|
|
Pulling eye
|
Stainless steel, sized for hotstick switching so the elbow can be parked without a live-front operation.
|
|
Ground lead
|
#4 AWG flexible copper stranded, woven construction, rated to carry the surge current to ground.
|
|
Stainless steel cap
|
Closes the test point / interface end against moisture ingress.
|
Every unit is tested before shipment; the MOV blocks are additionally sampled on a batch basis.
| Elbow arrester — 100% of units | MOV module — batch and periodic |
|---|---|
|
Partial discharge test
|
Partial discharge test
|
|
Voltage at 1 mA
|
Voltage at 1 mA
|
|
Leakage current
|
Leakage current
|
|
Physical inspection
|
Batch high-current, short-duration test
|
|
Periodic dissection
|
Batch thermal stability test
|
|
Periodic X-ray analysis
|
Batch aging test
|
|
—
|
Physical inspection
|
▪ The MCOV of the arrester must be at least the maximum continuous line-to-ground voltage at the point of installation — including any sustained overvoltage from single-phasing or ferroresonance.
▪ The protective level at the cable end must stay below the basic impulse level (BIL) of the cable and of the connected transformer, with margin for lead length.
▪ Elbow arresters protect the cable at the open point. They do not replace transformer-mounted arresters inside the tank.
▪ Torque and interface preparation follow IEEE Std 386 practice: clean, grease, push, and confirm the elbow is fully seated on the bushing.
▪ Ratings shown are for reference. Confirm the final selection against the latest Chardon data sheet and the project insulation coordination study.
The same elbow arrester is available in 15 kV and 25 kV small interface versions (15-LEA and 25-LEA) for lower system voltages. Grounding elbows and loadbreak elbows for the same 35 kV large interface system are listed separately.
Product Code: 35L-LEA35 kV large interface elbow arrester to IEEE Std 386. Metal oxide varistor module moulded in a peroxide-cured EPDM rubber elbow, fully shielded and deadfront, for pad-mounted transformer and vault applications. Nine duty-cycle ratings from 10 kV to 36 kV.
200A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
165A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
140A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
125A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
100A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
80A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
65A 38.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
100A 23.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.
80A 23.0kV, ABB Backup Current Limiting Fuse (Trans-Guard OS Shorty type), ANSI/IEEE C37.40 partial-range backup fuse for oil-immersed distribution transformers.